KFP-CF2-SC-xx - Conventional Fire Panel with User Interface with Scandinavian Key - 2 Zone

Description

The KFP-CF2-SC is a conventional fire alarm control panel with Scandinavian key support. It is supplied in local language with 2 zones that support up to 20 devices per zone, as well as up to 2 supervised relay outputs dedicated to sounder control. In addition 2 conventional relay outputs dedicated to common fire and fault conditions, as well as two user configurable inputs for monitoring and control are available.

KFP-C fire control panels offer state of the art architecture in configurations that deliver an uncomplicated solution for small to mid-sized conventional applications. They feature an attractive contemporary design that fits with any decor. The gently curved door front offers a distinctive flair. Operator controls are inset in a striking grey lexan.

With a comprehensive line of conventional devices and accessories, these quick-to-configure systems offer versatility that benefits building owners and installation/maintenance companies alike.

Technical specs

Input Supply
  110 VAC/60 Hz or 240 VAC/50 Hz
 Tolerance
  +10% / -15%
 Current consumption (max)
  2A @ 110/240 VAC
 Cable specification
  3 x 1.5 mm² (live, neutral, earth)
Batteries
  2 x 12V - 7.2 Ah (SLA)
Panel Supply
  2A @ 24 VDC
 Quiescent current (no devices)
  50 mA
 Alarm current (no devices)
  130 mA
Zones
  2
 Output voltage
  22 VDC (18-24 VDC)
 Load (max)
  65 mA
 Cable resistance (max)
  40 ohm
 Cable capacitance (max)
  500 nF
 Devices per zone (max)
  20
Inputs
  2
 Cable resistance (max)
  100 ohm
Supervised Outputs
  2
 Output voltage
  -15 to +28 VDC
 Load (max)
  250 mA
Non Supervised Outputs
  2
 Load
  2 A @ 30 VDC
Auxilliary Supply Output
 
 Output voltage
  24 VDC (21 to 28 VDC)
 Load (max)
  250 mA
Environmental
 
 Storage temperature
  -20 to +70°C
 Operating temperature
  -5 to +50°C *
 Relative humidity (noncondensing)
  10 to 95%
 IP Rating
  IP30
Mechanical
 
 Size (h x w x d)
  435 x 320 x 129 mm
 Weight (without batteries)
  2.8 kg
 Colour
  RAL9010
 Cable entry (top / bottom / rear)
  Ø 20 mm - 14 / 2 / 12
 
 
* Special conditions apply
 
 
 
  • Modern, elegant design
  • Easy removable parts for quick and clean installation
  • Default regional setup modes
  • Supervised alarm notification outputs
  • EN54 compliant potential free fire & fault relays
  • Remote sounder control, day/night & reset facilities
  • Auxiliary 24VDC supply output with reset support
  • Default support for special functions such as: - EN54 compliant user access levels - mixed zones - full front panel diagnostics - one-man walk test
  • Auxiliary standard & supervised relay output boards
  • Networkable up to 64 zones